Galaxy Helios
- Partly in service
- AI/HPC campus
- 8 sources
- Last checked Sep 24, 2026
Key facts
Each value says what backs it, then how much weight it bears: Sourced (a cited source states it), Calculated (DCRA did the math, shown), or Unknown (not in the public record); then strong, fair, or weak. Weak labels are highlighted.
What the labels mean
- Sourced
- A cited source states it. Open the source to see who said it.
- Calculated
- DCRA calculated it from sourced values. The math is shown.
- Estimate
- An approximation where no source states the value.
- Modeled
- Output of an illustrative planning scenario. Not a forecast.
- Unknown
- Not in the public record. Unknown, not absent.
- Sourced · strong
- Strong: read directly in a primary record, such as a filing or the company's own release.
- Sourced · fair
- Fair: a company statement of its own plans, an official's written reply, or a solid report.
- Sourced · weak
- Highlighted. Weak: a secondhand account, a search excerpt, or a value that may be out of date.
The words are display only. The records and the dataset keep the original values (VERIFIED, DERIVED, ESTIMATED, MODELED, UNKNOWN; HIGH, MODERATE, LOW): Sourced is VERIFIED, Calculated is DERIVED, and strong, fair, and weak are HIGH, MODERATE, and LOW.
- Status
- Phase I delivered · expanding
- Sourced · fair
- (Electric Reliability Council of Texas)ERCOT (Electric Reliability Council of Texas): Runs the power grid that serves most of Texas and reviews requests to connect very large new users. It does not own power lines.-approved capacity
- 1,630 (megawatt)MW (megawatt): A measure of power at one moment. 1,000 MW is 1 GW (gigawatt). Energy used over time is measured in megawatt-hours (MWh). approved
- Sourced · strong
- Delivered critical IT (Phase I)
- 133 MW IT (200 MW gross)
- Sourced · fair
- Campus footprint
- 1,500+ acres
- Sourced · fair
- Tenant
- CoreWeave (15-year leases)
- Sourced · strong
"Not in the public record" means unknown, not absent. How DCRA sources and labels its records.
Plain-language glossary: 8 terms used on this page
- ERCOT (Electric Reliability Council of Texas)
- Runs the power grid that serves most of Texas and reviews requests to connect very large new users. It does not own power lines.
- PUCT (Public Utility Commission of Texas)
- The state agency that regulates electric utilities, including the rules for who pays for grid equipment.
- TCRF (transmission cost recovery factor)
- A charge on Texas electric bills that passes changes in transmission costs on to customers, updated twice a year.
- SB 6 (Senate Bill 6)
- A state law setting rules for very large electricity users, including what they must pay toward their own grid connection.
- Interconnection agreement
- The contract with the utility to connect a large user to the grid, setting how much power the connection is sized for.
- MW (megawatt)
- A measure of power at one moment. 1,000 MW is 1 GW (gigawatt). Energy used over time is measured in megawatt-hours (MWh).
- kV (kilovolt)
- A measure of a power line's voltage. Higher-voltage lines, such as 138 kV or 345 kV, carry more power over longer distances.
- UPS (uninterruptible power supply)
- Batteries that keep computers running through the seconds between a power loss and backup generators starting.
Profile
Galaxy's Helios campus in Dickens County, about 60 miles from Lubbock, has 1,630 MW of ERCOT-approved capacity. Phase I (133 MW of critical IT, 200 MW gross) was delivered to CoreWeave in 2026 under 15-year leases. Sourced · fair
Power and the grid
What published records say about supplying this data center, and how its planned power compares in size with local demand today. A size comparison is not a grid study. Each label opens its sources.
Loading grid records…
Published grid documents and the capacity comparison are in the interactive atlas, under Energy.
Who pays for the grid equipment
Substations, lines, and transformers filed for this data center or its area, what each is filed to cost, and who the rules and documents say pays. Only filed or published documents are used; a cost with no document is unknown.
Filed grid projects
No filed substation, line, or transformer project is recorded for this facility yet. That means none has been researched or found, not that none exists.
Who pays for this facility's connection
Unknown No filed document or company statement recorded by DCRA says who paid, or will pay, for this facility's connection.
The rules · ERCOT, TX
- New lines and transmission substations In force
- Pays: Electricity users across the grid region. Equipment at 60 (kilovolt)kV (kilovolt): A measure of a power line's voltage. Higher-voltage lines, such as 138 kV or 345 kV, carry more power over longer distances. and above is paid for by electricity users across all of ERCOT, not only nearby. Each transmission utility's approved cost is shared among every distribution utility in ERCOT by its share of the summer peak. Sourced · strongPublic Utility Commission of Texas
- On household bills In force
- Pays: The utility's customers. Distribution utilities pass changes in those transmission charges on to their customers twice a year. Sourced · strongPublic Utility Commission of Texas
- What a large data center pays itself In force
- Pays: The data center or its developer. Texas (Senate Bill 6)SB 6 (Senate Bill 6): A state law setting rules for very large electricity users, including what they must pay toward their own grid connection. (2025) requires loads of 75 MW and up (the default threshold) to contribute to the utility's cost of connecting them, pay a screening study fee of at least $100,000, and post financial security for transmission built to serve them. Sourced · strongTexas Legislature
- Proposed change Proposed
- Pays: Electricity users across the grid region. In July 2026 the (Public Utility Commission of Texas)PUCT (Public Utility Commission of Texas): The state agency that regulates electric utilities, including the rules for who pays for grid equipment. proposed sharing transmission cost by 12 monthly peaks instead of 4 summer ones, with a minimum bill for large loads. Adoption is not confirmed. Sourced · strongPublic Utility Commission of Texas (Texas Register, July 24, 2026)
- This facility's share
- Unknown How much of any planned line or upgrade a single facility pays is not published; the rules above name no customer.
Hazards
Materials a data center like this may hold, sorted by what is known about this one: confirmed at this facility, or only typical of the equipment and not confirmed here. A short reference, not a safety data sheet.
What this facility's record says
- Battery / (uninterruptible power supply)UPS (uninterruptible power supply): Batteries that keep computers running through the seconds between a power loss and backup generators starting. system
- Not in the public record
- Backup generation
- Not in the public record
Lithium-ion batteries
Associated with equipment category · not verified hereAssociated with the data-center equipment category; not verified at this facility. Unknown
Firefighting considerations and references
- Batteries may re-ignite after apparent extinguishment; extended monitoring is a planning consideration.
- Large volumes of water for cooling are frequently cited; the NIRS 2025 incident reported submersion of battery packs in water tanks.
- Site pre-plans, facility subject-matter experts, and installation documentation (NFPA 855, UL 9540A results) are the appropriate inputs for tactics.
Diesel fuel
Associated with equipment category · not verified hereAssociated with the data-center equipment category; not verified at this facility. Unknown
Firefighting considerations and references
- Foam and fuel-fire tactics apply to pool fires; tank quantity and containment design are UNKNOWN at Beacon Point.
Transformer insulating fluid
Associated with equipment category · not verified hereAssociated with the data-center equipment category; not verified at this facility. Unknown
Firefighting considerations and references
- Energized equipment: coordinate isolation with the utility before direct attack.
Emergency response
The fire department responsible for this site and the recorded fire stations and hospitals nearby, by straight-line distance from the approximate facility point. Not a dispatch order, response time, or first-due determination; mutual-aid roles are potential only. A capability missing from the public record is unknown, not absent.
Fire jurisdiction
- Primary fire jurisdiction
- Not in the public record
Fire and rescue stations (14)
| Name | Straight-line distance | Role |
|---|---|---|
| Dickens Volunteer Fire Department | 0.5 mi ENE | Nearby origin |
| Spur Volunteer Fire Department | 10 mi S | Nearby origin |
| Matador Volunteer Fire Department | 27 mi N | Potential mutual-aid origin |
| Ralls Volunteer Fire Department | 31 mi W | Potential mutual-aid origin |
| Floydada Volunteer Fire Department | 38 mi NW | Potential mutual-aid origin |
| Lorenzo Volunteer Fire Department and Emergency Medical Services | 40 mi W | Potential mutual-aid origin |
| Paducah Volunteer Fire Department | 41 mi NE | Potential mutual-aid origin |
| Post Volunteer Fire Department | 43 mi SW | Potential mutual-aid origin |
| Petersburg Volunteer Emergency Medical Services | 47 mi WNW | Potential mutual-aid origin |
| Slaton Fire Department | 48 mi WSW | Potential mutual-aid origin |
Hospitals (2)
| Name | Straight-line distance | Emergency department |
|---|---|---|
| Stonewall Memorial Hospital | 48 mi SE | Not in the public record |
| W J Mangold Memorial Hospital | 49 mi NW | Not in the public record |
Sources for these stations and hospitals (2)
What this record is missing
No public source yet for:
- Site location (only a county-level point is shown)
- Cooling method and water source
- Local response resources not yet recorded
Changes (1)
- 2026-09-24 Added to the atlas Galaxy Helios: Added to the atlas.